Industrial buildings are where a general-purpose extinguisher on a bracket stops being good enough. The hazard drives the class, the rating and — most importantly — how far somebody is allowed to walk to reach one.
This is the single most misunderstood requirement in a racked building. The 75-foot limit for Class A hazards is the distance somebody actually walks — down the aisle, around the end of the racking, across the floor. It is not the straight-line distance on a floor plan.
That means a warehouse can be reconfigured into non-compliance without anybody touching an extinguisher. New racking, a changed aisle layout or a tenant fit-out all move the walking route. The survey has to be re-walked, not assumed.
Detection in a high-bay space behaves differently from detection in an office. Smoke stratifies and takes far longer to reach a ceiling-mounted detector, which is why beam detection and other approaches are used in tall buildings. If your warehouse has standard spot detectors at roof level, it is worth a conversation about whether they will actually see a fire in time.